1x240

Description

Description

Standards

  • Product
    IEC 60502-1
  • Test
    IEC 60332-1

Application


These power cables are used for electricity supply in low voltage installation systems.

They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant…)

 

Design

 

  1. Conductor
    Stranded bare copper class 2 acc. to IEC 60228
     
  2. Insulation
    Cross Linked Polyethylene "XLPE"
     
  3. Inner Sheath or Bedding
    Lapped bedding or extruded HFFR 
     
  4. Armour
    Aluminum Steel Wire Armour "AWA"
  1. Outer Sheath 
    Halogen Free Flame retardant "HFFR".

      Options :

             - Flame retardant : "CAT A, CAT B, CAT C" to IEC60332 or equivalent.

             - Ozone resistant.

             - Oil resistant.

             - Anti termite.

 Installation Conditions:

  1. Air Temperature : 30 Deg.
  2. Ground Temperature: 20 Deg.
  3. Soil Thermal Resistivity : 2.5 k.m/w
  4. Depth of lay : 0.7 m

 All dimensions have tolerance +- 7 %

Marking

no. of cores x conductor sizes mm2 Cu / XLPE / AWA / HFFR 600/1000 V IEC 60502-1   MADE IN QATAR QICC-Nexans Year Meters

Custom marking available

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
-
Insulation
XLPE (Cross-linked Polyethylene)
Inner sheath
Halogen free flame retardant
Armour type
Aluminium Wire
Outer sheath
HFFR (Halogen Free Flame Retardant)
Colour
Black
Halogen free
Yes
Conductor flexibility
Stranded class 2

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Conductor cross-section
240 mm²
Approximate weight
2660 kg/km
Ground conductor cross-section
- mm²
Nominal outer diameter
31.0 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV
Max. DC resistance of the conductor at 20°C
0.0754 Ohm/km
Permissible current rating in open air
634 A
Permissible current rating when buried
375 A
Voltage drop, 3 conductors
- V/A.km
Voltage drop, single phase
0.25 V/A.km

Mechanical characteristics

Mechanical characteristics

Cable flexibility
-

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when laying
15 (xD)
Bending factor when installed
8 (xD)
Smoke density
IEC 61034
Gases corrosivity
IEC 60754-2

Resources

Resources

Selling & delivery Information

Marking

no. of cores x conductor sizes mm2 Cu / XLPE / AWA / HFFR 600/1000 V IEC 60502-1   MADE IN QATAR QICC-Nexans Year Meters

Custom marking available

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close