ALSECURE® IEC LV, XLPE Insulation, AWA, HFFR 0.6/1 kV
ALSECURE® IEC LV, XLPE Insulation, AWA, HFFR 0.6/1 kV
Aluminum wire armoured LV cable, HFFR sheathed for fixed installations. Rated voltage 0.6/1 KV
Read more1x120
Nexans ref. 21120BXZVAB09BD0
- Conductor cross-section: 120 mm²
- Approximate weight: 1460 kg/km
- Nominal outer diameter: 25.0 mm
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Permissible current rating in open air: 400 A
- Permissible current rating when buried: 257 A
- Voltage drop, single phase: 0.39 V/A.km
1x150
Nexans ref. 21150BXZVAB09BD0
- Conductor cross-section: 150 mm²
- Approximate weight: 1750 kg/km
- Nominal outer diameter: 26.0 mm
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Permissible current rating in open air: 464 A
- Permissible current rating when buried: 287 A
- Voltage drop, single phase: 0.34 V/A.km
1x185
Nexans ref. 21185BXZVAB09BD0
- Conductor cross-section: 185 mm²
- Approximate weight: 2100 kg/km
- Nominal outer diameter: 28.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Permissible current rating in open air: 533 A
- Permissible current rating when buried: 324 A
- Voltage drop, single phase: 0.29 V/A.km
1x240
Nexans ref. 21240BXZVAB09BD0
- Conductor cross-section: 240 mm²
- Approximate weight: 2660 kg/km
- Nominal outer diameter: 31.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- Permissible current rating in open air: 634 A
- Permissible current rating when buried: 375 A
- Voltage drop, single phase: 0.25 V/A.km
1x300
Nexans ref. 21300BXZVAB09BD0
- Conductor cross-section: 300 mm²
- Approximate weight: 3230 kg/km
- Nominal outer diameter: 33.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
- Permissible current rating in open air: 736 A
- Permissible current rating when buried: 419 A
- Voltage drop, single phase: 0.22 V/A.km
1x400
Nexans ref. 21400BXZVAB09BD0
- Conductor cross-section: 400 mm²
- Approximate weight: 4110 kg/km
- Nominal outer diameter: 37.0 mm
- Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
- Permissible current rating in open air: 868 A
- Permissible current rating when buried: 717 A
- Voltage drop, single phase: 0.19 V/A.km
1x500
Nexans ref. 21500BXZVAB09BD0
- Conductor cross-section: 500 mm²
- Approximate weight: 5225 kg/km
- Nominal outer diameter: 42.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0366 Ohm/km
- Permissible current rating in open air: 998 A
- Permissible current rating when buried: 791 A
- Voltage drop, single phase: 0.17 V/A.km
1x630
Nexans ref. 21630BXZVAB09BD0
- Conductor cross-section: 630 mm²
- Approximate weight: 6510 kg/km
- Nominal outer diameter: 46.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0283 Ohm/km
- Permissible current rating in open air: 1151 A
- Permissible current rating when buried: 861 A
- Voltage drop, single phase: 0.16 V/A.km
1x70
Nexans ref. 21070BXZVAB09BD0
- Conductor cross-section: 70 mm²
- Approximate weight: 940 kg/km
- Nominal outer diameter: 21.0 mm
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Permissible current rating in open air: 278 A
- Permissible current rating when buried: 188 A
- Voltage drop, single phase: 0.61 V/A.km
1x800
Nexans ref. 21800BXZVAB09BD0
- Conductor cross-section: 800 mm²
- Approximate weight: 8340 kg/km
- Nominal outer diameter: 50.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0221 Ohm/km
- Permissible current rating in open air: 1246 A
- Permissible current rating when buried: 904 A
- Voltage drop, single phase: 0.15 V/A.km
1x95
Nexans ref. 21095BXZVAB09BD0
- Conductor cross-section: 95 mm²
- Approximate weight: 1210 kg/km
- Nominal outer diameter: 23.0 mm
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Permissible current rating in open air: 342 A
- Permissible current rating when buried: 226 A
- Voltage drop, single phase: 0.47 V/A.km
Description
Description
Standards
-
ProductIEC 60502-1
-
TestIEC 60332-1
Application
These power cables are used for electricity supply in low voltage installation systems.
They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant…)
Design
- Conductor
Stranded bare copper class 2 acc. to IEC 60228
- Insulation
Cross Linked Polyethylene "XLPE"
- Inner Sheath or Bedding
Lapped bedding or extruded HFFR
- Armour
Aluminum Steel Wire Armour "AWA"
- Outer Sheath
Halogen Free Flame retardant "HFFR".
Options :
- Flame retardant : "CAT A, CAT B, CAT C" to IEC60332 or equivalent.
- Ozone resistant.
- Oil resistant.
- Anti termite.
Installation Conditions:
- Air Temperature : 30 Deg.
- Ground Temperature: 20 Deg.
- Soil Thermal Resistivity : 2.5 k.m/w
- Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Selling & delivery Information
Marking
no. of cores x conductor sizes mm2 Cu / XLPE / AWA / HFFR 600/1000 V IEC 60502-1 MADE IN QATAR QICC-Nexans Year Meters