EN 50288-7 Silicone IOS Armoured LC 20x2x0,5
EN 50288-7 Silicone IOS Armoured LC 20x2x0,5
- Instrumentation cables 170/300 V
- With lead cover (LC)
- Individual & Overall Screen (IOS)
- Aliphatic and aromatic hydrocarbons resistant
- Nexans ref. : 10135236
- EAN : 3427580322778
Description
Description
Standards
-
TestIEC 60331; IEC 60332-3-22 Cat.A
Applications
These instrumentation and communication cables are used to transmit analogue or digital signals in measurement and process control. They are well adapted to underground use in industrial applications, in moist areas, where hydrocarbon and mechanical protection are needed. The lead cover brings an enhanced resistance to aromatics hydrocarbons. The individual screening of each pair limits the consequence of crosstalk. They maintain circuit integrity when exposed to fire.
Design
Conductor:
Stranded bare copper class 2
Insulation:
Silicone rubber (Sil)
Individual screen:
Polyester tape
Tinned copper drain wire
Aluminium backed polyester tape
Polyester tape
Overall screen:
Polyester tape
Tinned copper drain wire
Aluminium backed polyester tape
Inner sheath:
Low Smoke Zero Halogen (LSZH)
Colour: black
Lead sheath:
Bedding (intermediate sheath):
Polyvinyl chloride (PVC)
Colour: black
Armour:
Galvanized steel wires (SWA)
Outer sheath:
Polyvinyl chloride (PVC)
Colour: black
Other colour on request.
Core identification
Pair: white - black
White core printed with pair number
Marking
NEXANS 279 SIL/IND.+OA.SCR/LSZH//LC/PVC/SWA/PVC 170/300V Nber of pairs & cross-section Cu IEC 60331 IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking
Standards
EN 50288-7 (Design guide-lines)
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Documentation
Selling & delivery Information
Other fire performances IEC 60332-1 or IEC 60332-3-24(C) on request.
Minimum bending radius:
10 x outer diameter
To be doubled during laying operations
Tinned copper conductors available on request
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania