EN 50288-7 XLPE OS Armoured 20x2x1,5

Description

Description

Standards

  • Test
    IEC 60332-3-22 Cat.A

Applications

These instrumentation and communication cable are used to transmit analogue or digital signals in measurement and process control .They are well adapted to underground use in industrial application where chemical and mechanical protections are needed (refinery areas, chemical plan…) .

 

Design

Conductor:

Stranded bare copper class 2

Insulation:

Cross-linked polyethylene (XLPE)

Overall screen

Polyester tape

Tinned copper drain wire, 

Aluminium backed polyester tape

Inner sheath:

Polyvinyl chloride (PVC).

Colour : black

Armour:

Galvanized steel wires (SWA)

Outer sheath:

Polyvinyl chloride (PVC). 

Colour: black. 

Other colour on request.

 

Core identification

Pair:  white - black
Quad: white - black - red - blue (2 pair cables assembled as a quad)
White core printed with pair number
 

Marking

NEXANS 279 XLPE/OA.SCR/PVC/SWA/PVC 170/300V Nber of pairs & cross-section Cu IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking

 

Standards

 EN 50288-7 (design guide-lines)

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Bare copper
Type of conductor
Stranded, class 2
Insulation
XLPE (Cross-linked Polyethylene)
Overall screen
Tinned copper drain wire + aluminium/polyester tape
Inner sheath
PVC
Armour type
Galvanized steel wires
Outer sheath
PVC
Protection
Yes

Dimensional characteristics

Dimensional characteristics

Number of pairs
20
Conductor cross-section
1.5 mm²
Conductor diameter
1.5 mm
Diameter over insulation
2.16 mm
Diameter over inner sheath
22.7 mm
Diameter over armour
25.2 mm
Minimum outer diameter
27.7 mm
Maximum outer diameter
30.6 mm
Approximate weight
1500 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
170/300V

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Fire retardant
EN IEC 60332-3-22 (cat A)
Oil resistance
Yes
Electro magnetic interference resistance
Yes
Operating temperature, range
-20 ... 60 °C
Max. conductor temperature in service
90 °C
Standard
EN

Resources

Resources

Documentation

Selling & delivery Information


Other fire performances IEC 60332-1 or IEC 60332-3-24(C) and enhanced hydrocarbon resistance on request.


Minimum bending radius:

10 x outer diameter
To be doubled during laying operations


Tinned copper conductors available on request

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close