IEC LV, XLPE Insulation, PVC 0.6/1KV
IEC LV, XLPE Insulation, PVC 0.6/1KV
Unarmoured LV cable, PVC sheathed for fixed installations. Rated voltage 0.6/1 KV
Read more12x1.5
Nexans ref. 2E002BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 12
- Conductor cross-section: 1.5 mm²
- Approximate weight: 480 kg/km
- Nominal outer diameter: 18.0 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Permissible current rating in open air: 23 A
- Permissible current rating when buried: 21 A
- Voltage drop, 3 conductors: 22.8 V/A.km
12x2.5
Nexans ref. 2E003BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 12
- Conductor cross-section: 2.5 mm²
- Approximate weight: 640 kg/km
- Nominal outer diameter: 19.0 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 32 A
- Permissible current rating when buried: 30 A
- Voltage drop, 3 conductors: 14.0 V/A.km
19x1.5
Nexans ref. 2F002BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 19
- Conductor cross-section: 1.5 mm²
- Approximate weight: 655 kg/km
- Nominal outer diameter: 20.0 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Permissible current rating in open air: 23 A
- Permissible current rating when buried: 21 A
- Voltage drop, 3 conductors: 22.8 V/A.km
19x2.5
Nexans ref. 2F003BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 19
- Conductor cross-section: 2.5 mm²
- Approximate weight: 880 kg/km
- Nominal outer diameter: 22.0 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 32 A
- Permissible current rating when buried: 30 A
- Voltage drop, 3 conductors: 14.0 V/A.km
1x10
Nexans ref. 21010BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 1
- Conductor cross-section: 10 mm²
- Approximate weight: 160 kg/km
- Nominal outer diameter: 8.0 mm
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Permissible current rating in open air: 85 A
- Permissible current rating when buried: 77 A
- Voltage drop, 3 conductors: 3.6 V/A.km
1x120
Nexans ref. 21120BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 1
- Conductor cross-section: 120 mm²
- Approximate weight: 1140 kg/km
- Nominal outer diameter: 18.0 mm
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Permissible current rating in open air: 400 A
- Permissible current rating when buried: 306 A
- Voltage drop, 3 conductors: 0.38 V/A.km
1x150
Nexans ref. 21150BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 1
- Conductor cross-section: 150 mm²
- Approximate weight: 1400 kg/km
- Nominal outer diameter: 20.0 mm
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Permissible current rating in open air: 464 A
- Permissible current rating when buried: 343 A
- Voltage drop, 3 conductors: 0.33 V/A.km
1x16
Nexans ref. 21016BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 1
- Conductor cross-section: 16 mm²
- Approximate weight: 220 kg/km
- Nominal outer diameter: 9.0 mm
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Permissible current rating in open air: 113 A
- Permissible current rating when buried: 100 A
- Voltage drop, 3 conductors: 2.3 V/A.km
1x185
Nexans ref. 21185BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 1
- Conductor cross-section: 185 mm²
- Approximate weight: 1740 kg/km
- Nominal outer diameter: 22.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Permissible current rating in open air: 533 A
- Permissible current rating when buried: 387 A
- Voltage drop, 3 conductors: 0.28 V/A.km
1x240
Nexans ref. 21240BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 1
- Conductor cross-section: 240 mm²
- Approximate weight: 2250 kg/km
- Nominal outer diameter: 25.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- Permissible current rating in open air: 634 A
- Permissible current rating when buried: 448 A
- Voltage drop, 3 conductors: 0.24 V/A.km
1x25
Nexans ref. 21025BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 1
- Conductor cross-section: 25 mm²
- Approximate weight: 330 kg/km
- Nominal outer diameter: 11.0 mm
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Permissible current rating in open air: 135 A
- Permissible current rating when buried: 129 A
- Voltage drop, 3 conductors: 1.5 V/A.km
1x300
Nexans ref. 21300BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 1
- Conductor cross-section: 300 mm²
- Approximate weight: 2780 kg/km
- Nominal outer diameter: 27.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
- Permissible current rating in open air: 736 A
- Permissible current rating when buried: 502 A
- Voltage drop, 3 conductors: 0.21 V/A.km
1x35
Nexans ref. 21035BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 1
- Conductor cross-section: 35 mm²
- Approximate weight: 425 kg/km
- Nominal outer diameter: 12.0 mm
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Permissible current rating in open air: 169 A
- Permissible current rating when buried: 155 A
- Voltage drop, 3 conductors: 1.1 V/A.km
1x400
Nexans ref. 21400BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 1
- Conductor cross-section: 400 mm²
- Approximate weight: 3530 kg/km
- Nominal outer diameter: 31.0 mm
- Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
- Permissible current rating in open air: 868 A
- Permissible current rating when buried: 717 A
- Voltage drop, 3 conductors: 0.18 V/A.km
1x50
Nexans ref. 21050BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 1
- Conductor cross-section: 50 mm²
- Approximate weight: 480 kg/km
- Nominal outer diameter: 13.0 mm
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Permissible current rating in open air: 216 A
- Permissible current rating when buried: 183 A
- Voltage drop, 3 conductors: 0.83 V/A.km
1x500
Nexans ref. 21500BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 1
- Conductor cross-section: 500 mm²
- Approximate weight: 4570 kg/km
- Nominal outer diameter: 35.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0366 Ohm/km
- Permissible current rating in open air: 896 A
- Permissible current rating when buried: 539 A
- Voltage drop, 3 conductors: 0.16 V/A.km
1x630
Nexans ref. 21630BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 1
- Conductor cross-section: 630 mm²
- Approximate weight: 5810 kg/km
- Nominal outer diameter: 39.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0283 Ohm/km
- Permissible current rating in open air: 1035 A
- Permissible current rating when buried: 678 A
- Voltage drop, 3 conductors: 0.15 V/A.km
1x70
Nexans ref. 21070BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 1
- Conductor cross-section: 70 mm²
- Approximate weight: 670 kg/km
- Nominal outer diameter: 15.0 mm
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Permissible current rating in open air: 279 A
- Permissible current rating when buried: 225 A
- Voltage drop, 3 conductors: 0.6 V/A.km
1x800
Nexans ref. 21800BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 1
- Conductor cross-section: 800 mm²
- Approximate weight: 7375 kg/km
- Nominal outer diameter: 43.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0221 Ohm/km
- Permissible current rating in open air: 1246 A
- Permissible current rating when buried: 726 A
- Voltage drop, 3 conductors: 0.14 V/A.km
1x95
Nexans ref. 21095BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 1
- Conductor cross-section: 95 mm²
- Approximate weight: 920 kg/km
- Nominal outer diameter: 16.0 mm
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Permissible current rating in open air: 342 A
- Permissible current rating when buried: 270 A
- Voltage drop, 3 conductors: 0.46 V/A.km
24x1.5
Nexans ref. 2I002BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 24
- Conductor cross-section: 1.5 mm²
- Approximate weight: 860 kg/km
- Nominal outer diameter: 23.0 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Permissible current rating in open air: 23 A
- Permissible current rating when buried: 21 A
- Voltage drop, 3 conductors: 22.8 V/A.km
24x2.5
Nexans ref. 2I003BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 24
- Conductor cross-section: 2.5 mm²
- Approximate weight: 1150 kg/km
- Nominal outer diameter: 26.0 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 32 A
- Permissible current rating when buried: 30 A
- Voltage drop, 3 conductors: 14.0 V/A.km
2x1.5
Nexans ref. 22002BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 2
- Conductor cross-section: 1.5 mm²
- Approximate weight: 175 kg/km
- Nominal outer diameter: 11.0 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Permissible current rating in open air: 23 A
- Permissible current rating when buried: 21 A
- Voltage drop, 3 conductors: 22.8 V/A.km
2x10
Nexans ref. 22010BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 2
- Conductor cross-section: 10 mm²
- Approximate weight: 440 kg/km
- Nominal outer diameter: 16.0 mm
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Permissible current rating in open air: 75 A
- Permissible current rating when buried: 65 A
- Voltage drop, 3 conductors: 3.5 V/A.km
2x120
Nexans ref. 22120BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 2
- Conductor cross-section: 120 mm²
- Approximate weight: 3240 kg/km
- Nominal outer diameter: 37.0 mm
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Permissible current rating in open air: 346 A
- Permissible current rating when buried: 257 A
- Voltage drop, 3 conductors: 0.37 V/A.km
2x150
Nexans ref. 22150BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 2
- Conductor cross-section: 150 mm²
- Approximate weight: 3960 kg/km
- Nominal outer diameter: 41.0 mm
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Permissible current rating in open air: 399 A
- Permissible current rating when buried: 287 A
- Voltage drop, 3 conductors: 0.31 V/A.km
2x16
Nexans ref. 22016BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 2
- Conductor cross-section: 16 mm²
- Approximate weight: 570 kg/km
- Nominal outer diameter: 18.0 mm
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Permissible current rating in open air: 100 A
- Permissible current rating when buried: 84 A
- Voltage drop, 3 conductors: 2.2 V/A.km
2x185
Nexans ref. 22185BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 2
- Conductor cross-section: 185 mm²
- Approximate weight: 4980 kg/km
- Nominal outer diameter: 46.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Permissible current rating in open air: 456 A
- Permissible current rating when buried: 324 A
- Voltage drop, 3 conductors: 0.27 V/A.km
2x2.5
Nexans ref. 22003BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 2
- Conductor cross-section: 2.5 mm²
- Approximate weight: 220 kg/km
- Nominal outer diameter: 12.0 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 32 A
- Permissible current rating when buried: 30 A
- Voltage drop, 3 conductors: 14.0 V/A.km
2x25
Nexans ref. 22025BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 2
- Conductor cross-section: 25 mm²
- Approximate weight: 840 kg/km
- Nominal outer diameter: 21.0 mm
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Permissible current rating in open air: 127 A
- Permissible current rating when buried: 107 A
- Voltage drop, 3 conductors: 1.5 V/A.km
2x35
Nexans ref. 22035BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 2
- Conductor cross-section: 35 mm²
- Approximate weight: 1070 kg/km
- Nominal outer diameter: 23.0 mm
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Permissible current rating in open air: 158 A
- Permissible current rating when buried: 129 A
- Voltage drop, 3 conductors: 1.1 V/A.km
2x4
Nexans ref. 22004BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 2
- Conductor cross-section: 4 mm²
- Approximate weight: 270 kg/km
- Nominal outer diameter: 13.0 mm
- Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
- Permissible current rating in open air: 42 A
- Permissible current rating when buried: 39 A
- Voltage drop, 3 conductors: 8.7 V/A.km
2x50
Nexans ref. 22050BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 2
- Conductor cross-section: 50 mm²
- Approximate weight: 1400 kg/km
- Nominal outer diameter: 26.0 mm
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Permissible current rating in open air: 192 A
- Permissible current rating when buried: 153 A
- Voltage drop, 3 conductors: 0.81 V/A.km
2x6
Nexans ref. 22006BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 2
- Conductor cross-section: 6 mm²
- Approximate weight: 330 kg/km
- Nominal outer diameter: 14.0 mm
- Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
- Permissible current rating in open air: 54 A
- Permissible current rating when buried: 49 A
- Voltage drop, 3 conductors: 5.9 V/A.km
2x70
Nexans ref. 22070BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 2
- Conductor cross-section: 70 mm²
- Approximate weight: 1950 kg/km
- Nominal outer diameter: 30.0 mm
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Permissible current rating in open air: 246 A
- Permissible current rating when buried: 188 A
- Voltage drop, 3 conductors: 0.58 V/A.km
2x95
Nexans ref. 22095BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 2
- Conductor cross-section: 95 mm²
- Approximate weight: 2610 kg/km
- Nominal outer diameter: 33.0 mm
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Permissible current rating in open air: 298 A
- Permissible current rating when buried: 226 A
- Voltage drop, 3 conductors: 0.44 V/A.km
37x1.5
Nexans ref. 2M002BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 37
- Conductor cross-section: 1.5 mm²
- Approximate weight: 1130 kg/km
- Nominal outer diameter: 26.0 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Permissible current rating in open air: 23 A
- Permissible current rating when buried: 21 A
- Voltage drop, 3 conductors: 22.8 V/A.km
37x2.5
Nexans ref. 2M003BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 37
- Conductor cross-section: 2.5 mm²
- Approximate weight: 1550 kg/km
- Nominal outer diameter: 29.0 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 32 A
- Permissible current rating when buried: 30 A
- Voltage drop, 3 conductors: 14.0 V/A.km
3x1.5
Nexans ref. 23002BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 1.5 mm²
- Approximate weight: 185 kg/km
- Nominal outer diameter: 12.0 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Permissible current rating in open air: 23 A
- Permissible current rating when buried: 21 A
- Voltage drop, 3 conductors: 22.8 V/A.km
3x10
Nexans ref. 23010BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 10 mm²
- Approximate weight: 525 kg/km
- Nominal outer diameter: 17.0 mm
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Permissible current rating in open air: 75 A
- Permissible current rating when buried: 65 A
- Voltage drop, 3 conductors: 3.5 V/A.km
3x120
Nexans ref. 23120BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 120 mm²
- Approximate weight: 3430 kg/km
- Nominal outer diameter: 33.0 mm
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Permissible current rating in open air: 346 A
- Permissible current rating when buried: 257 A
- Voltage drop, 3 conductors: 0.37 V/A.km
3x120+70
Nexans ref. 27120BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 120 mm²
- Approximate weight: 4200 kg/km
- Nominal outer diameter: 39.0 mm
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Permissible current rating in open air: 346 A
- Permissible current rating when buried: 257 A
- Voltage drop, 3 conductors: 0.37 V/A.km
3x150
Nexans ref. 23150BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 150 mm²
- Approximate weight: 4240 kg/km
- Nominal outer diameter: 37.0 mm
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Permissible current rating in open air: 399 A
- Permissible current rating when buried: 287 A
- Voltage drop, 3 conductors: 0.31 V/A.km
3x150+70
Nexans ref. 27150BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 150 mm²
- Approximate weight: 5100 kg/km
- Nominal outer diameter: 43.0 mm
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Permissible current rating in open air: 399 A
- Permissible current rating when buried: 287 A
- Voltage drop, 3 conductors: 0.31 V/A.km
3x16
Nexans ref. 23016BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 16 mm²
- Approximate weight: 725 kg/km
- Nominal outer diameter: 19.0 mm
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Permissible current rating in open air: 100 A
- Permissible current rating when buried: 84 A
- Voltage drop, 3 conductors: 2.2 V/A.km
3x185
Nexans ref. 23185BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 185 mm²
- Approximate weight: 5250 kg/km
- Nominal outer diameter: 41.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Permissible current rating in open air: 456 A
- Permissible current rating when buried: 324 A
- Voltage drop, 3 conductors: 0.27 V/A.km
3x185+95
Nexans ref. 27185BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 185 mm²
- Approximate weight: 6300 kg/km
- Nominal outer diameter: 47.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Permissible current rating in open air: 456 A
- Permissible current rating when buried: 324 A
- Voltage drop, 3 conductors: 0.27 V/A.km
3x2.5
Nexans ref. 23003BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 2.5 mm²
- Approximate weight: 235 kg/km
- Nominal outer diameter: 13.0 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 32 A
- Permissible current rating when buried: 30 A
- Voltage drop, 3 conductors: 14.0 V/A.km
3x240
Nexans ref. 23240BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 240 mm²
- Approximate weight: 6730 kg/km
- Nominal outer diameter: 45.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- Permissible current rating in open air: 538 A
- Permissible current rating when buried: 375 A
- Voltage drop, 3 conductors: 0.23 V/A.km
3x240+120
Nexans ref. 27240BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 240 mm²
- Approximate weight: 7300 kg/km
- Nominal outer diameter: 53.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- Permissible current rating in open air: 538 A
- Permissible current rating when buried: 375 A
- Voltage drop, 3 conductors: 0.23 V/A.km
3x25
Nexans ref. 23025BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 25 mm²
- Approximate weight: 1060 kg/km
- Nominal outer diameter: 22.0 mm
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Permissible current rating in open air: 127 A
- Permissible current rating when buried: 107 A
- Voltage drop, 3 conductors: 1.5 V/A.km
3x25+16
Nexans ref. 27025BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 25 mm²
- Approximate weight: 1200 kg/km
- Nominal outer diameter: 24.0 mm
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Permissible current rating in open air: 127 A
- Permissible current rating when buried: 107 A
- Voltage drop, 3 conductors: 1.5 V/A.km
3x300
Nexans ref. 23300BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 300 mm²
- Approximate weight: 8450 kg/km
- Nominal outer diameter: 51.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
- Permissible current rating in open air: 621 A
- Permissible current rating when buried: 419 A
- Voltage drop, 3 conductors: 0.2 V/A.km
3x300+150
Nexans ref. 27300BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 300 mm²
- Approximate weight: 9000 kg/km
- Nominal outer diameter: 59.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
- Permissible current rating in open air: 621 A
- Permissible current rating when buried: 419 A
- Voltage drop, 3 conductors: 0.2 V/A.km
3x35
Nexans ref. 23035BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 35 mm²
- Approximate weight: 1380 kg/km
- Nominal outer diameter: 25.0 mm
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Permissible current rating in open air: 158 A
- Permissible current rating when buried: 129 A
- Voltage drop, 3 conductors: 1.1 V/A.km
3x35+16
Nexans ref. 27035BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 35 mm²
- Approximate weight: 1600 kg/km
- Nominal outer diameter: 20.0 mm
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Permissible current rating in open air: 158 A
- Permissible current rating when buried: 129 A
- Voltage drop, 3 conductors: 1.1 V/A.km
3x4
Nexans ref. 23004BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 4 mm²
- Approximate weight: 295 kg/km
- Nominal outer diameter: 14.0 mm
- Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
- Permissible current rating in open air: 42 A
- Permissible current rating when buried: 39 A
- Voltage drop, 3 conductors: 8.7 V/A.km
3x400
Nexans ref. 23400BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 400 mm²
- Approximate weight: 10800 kg/km
- Nominal outer diameter: 58.0 mm
- Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
- Permissible current rating in open air: 765 A
- Permissible current rating when buried: 468 A
- Voltage drop, 3 conductors: 0.18 V/A.km
3x400+185
Nexans ref. 27400BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 400 mm²
- Approximate weight: 11160 kg/km
- Nominal outer diameter: 65.0 mm
- Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
- Permissible current rating in open air: 765 A
- Permissible current rating when buried: 468 A
- Voltage drop, 3 conductors: 0.18 V/A.km
3x50
Nexans ref. 23050BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 50 mm²
- Approximate weight: 1435 kg/km
- Nominal outer diameter: 23.0 mm
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Permissible current rating in open air: 192 A
- Permissible current rating when buried: 153 A
- Voltage drop, 3 conductors: 0.81 V/A.km
3x50+25
Nexans ref. 27050BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 50 mm²
- Approximate weight: 1900 kg/km
- Nominal outer diameter: 27.0 mm
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Permissible current rating in open air: 192 A
- Permissible current rating when buried: 153 A
- Voltage drop, 3 conductors: 0.81 V/A.km
3x6
Nexans ref. 23006BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 6 mm²
- Approximate weight: 375 kg/km
- Nominal outer diameter: 15.0 mm
- Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
- Permissible current rating in open air: 54 A
- Permissible current rating when buried: 49 A
- Voltage drop, 3 conductors: 5.9 V/A.km
3x70
Nexans ref. 23070BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 70 mm²
- Approximate weight: 2020 kg/km
- Nominal outer diameter: 27.0 mm
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Permissible current rating in open air: 246 A
- Permissible current rating when buried: 188 A
- Voltage drop, 3 conductors: 0.58 V/A.km
3x70+35
Nexans ref. 27070BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 70 mm²
- Approximate weight: 2700 kg/km
- Nominal outer diameter: 30.0 mm
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Permissible current rating in open air: 246 A
- Permissible current rating when buried: 188 A
- Voltage drop, 3 conductors: 0.58 V/A.km
3x95
Nexans ref. 23095BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 95 mm²
- Approximate weight: 2745 kg/km
- Nominal outer diameter: 30.0 mm
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Permissible current rating in open air: 298 A
- Permissible current rating when buried: 226 A
- Voltage drop, 3 conductors: 0.44 V/A.km
3x95+50
Nexans ref. 27095BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 95 mm²
- Approximate weight: 3300 kg/km
- Nominal outer diameter: 34.0 mm
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Permissible current rating in open air: 298 A
- Permissible current rating when buried: 226 A
- Voltage drop, 3 conductors: 0.44 V/A.km
4x1.5
Nexans ref. 24002BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 4
- Conductor cross-section: 1.5 mm²
- Approximate weight: 210 kg/km
- Nominal outer diameter: 13.0 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Permissible current rating in open air: 23 A
- Permissible current rating when buried: 21 A
- Voltage drop, 3 conductors: 22.8 V/A.km
4x10
Nexans ref. 24010BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 4
- Conductor cross-section: 10 mm²
- Approximate weight: 635 kg/km
- Nominal outer diameter: 18.0 mm
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Permissible current rating in open air: 75 A
- Permissible current rating when buried: 65 A
- Voltage drop, 3 conductors: 3.5 V/A.km
4x120
Nexans ref. 24120BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 4
- Conductor cross-section: 120 mm²
- Approximate weight: 4480 kg/km
- Nominal outer diameter: 37.0 mm
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Permissible current rating in open air: 346 A
- Permissible current rating when buried: 257 A
- Voltage drop, 3 conductors: 0.37 V/A.km
4x150
Nexans ref. 24150BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 4
- Conductor cross-section: 150 mm²
- Approximate weight: 5530 kg/km
- Nominal outer diameter: 41.0 mm
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Permissible current rating in open air: 399 A
- Permissible current rating when buried: 287 A
- Voltage drop, 3 conductors: 0.31 V/A.km
4x16
Nexans ref. 24016BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 4
- Conductor cross-section: 16 mm²
- Approximate weight: 890 kg/km
- Nominal outer diameter: 20.0 mm
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Permissible current rating in open air: 100 A
- Permissible current rating when buried: 84 A
- Voltage drop, 3 conductors: 2.2 V/A.km
4x185
Nexans ref. 24185BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 4
- Conductor cross-section: 185 mm²
- Approximate weight: 6900 kg/km
- Nominal outer diameter: 46.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Permissible current rating in open air: 456 A
- Permissible current rating when buried: 324 A
- Voltage drop, 3 conductors: 0.27 V/A.km
4x2.5
Nexans ref. 24003BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 4
- Conductor cross-section: 2.5 mm²
- Approximate weight: 270 kg/km
- Nominal outer diameter: 14.0 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 32 A
- Permissible current rating when buried: 30 A
- Voltage drop, 3 conductors: 14.0 V/A.km
4x240
Nexans ref. 24240BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 4
- Conductor cross-section: 240 mm²
- Approximate weight: 8980 kg/km
- Nominal outer diameter: 51.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- Permissible current rating in open air: 538 A
- Permissible current rating when buried: 375 A
- Voltage drop, 3 conductors: 0.23 V/A.km
4x25
Nexans ref. 24025BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 4
- Conductor cross-section: 25 mm²
- Approximate weight: 1330 kg/km
- Nominal outer diameter: 24.0 mm
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Permissible current rating in open air: 127 A
- Permissible current rating when buried: 107 A
- Voltage drop, 3 conductors: 1.5 V/A.km
4x300
Nexans ref. 24300BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 4
- Conductor cross-section: 300 mm²
- Approximate weight: 11270 kg/km
- Nominal outer diameter: 58.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
- Permissible current rating in open air: 621 A
- Permissible current rating when buried: 419 A
- Voltage drop, 3 conductors: 0.2 V/A.km
4x35
Nexans ref. 24035BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 4
- Conductor cross-section: 35 mm²
- Approximate weight: 1730 kg/km
- Nominal outer diameter: 27.0 mm
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Permissible current rating in open air: 158 A
- Permissible current rating when buried: 129 A
- Voltage drop, 3 conductors: 1.1 V/A.km
4x4
Nexans ref. 24004BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 4
- Conductor cross-section: 4 mm²
- Approximate weight: 350 kg/km
- Nominal outer diameter: 15.0 mm
- Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
- Permissible current rating in open air: 42 A
- Permissible current rating when buried: 39 A
- Voltage drop, 3 conductors: 8.7 V/A.km
4x400
Nexans ref. 24400BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 4
- Conductor cross-section: 400 mm²
- Approximate weight: 14370 kg/km
- Nominal outer diameter: 65.0 mm
- Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
- Permissible current rating in open air: 765 A
- Permissible current rating when buried: 468 A
- Voltage drop, 3 conductors: 0.18 V/A.km
4x50
Nexans ref. 24050BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 4
- Conductor cross-section: 50 mm²
- Approximate weight: 1860 kg/km
- Nominal outer diameter: 25.0 mm
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Permissible current rating in open air: 192 A
- Permissible current rating when buried: 153 A
- Voltage drop, 3 conductors: 0.81 V/A.km
4x6
Nexans ref. 24006BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 4
- Conductor cross-section: 6 mm²
- Approximate weight: 440 kg/km
- Nominal outer diameter: 16.0 mm
- Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
- Permissible current rating in open air: 54 A
- Permissible current rating when buried: 49 A
- Voltage drop, 3 conductors: 5.9 V/A.km
4x70
Nexans ref. 24070BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 4
- Conductor cross-section: 70 mm²
- Approximate weight: 2630 kg/km
- Nominal outer diameter: 29.0 mm
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Permissible current rating in open air: 246 A
- Permissible current rating when buried: 188 A
- Voltage drop, 3 conductors: 0.58 V/A.km
4x95
Nexans ref. 24095BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 4
- Conductor cross-section: 95 mm²
- Approximate weight: 2610 kg/km
- Nominal outer diameter: 33.0 mm
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Permissible current rating in open air: 298 A
- Permissible current rating when buried: 226 A
- Voltage drop, 3 conductors: 0.44 V/A.km
5x1.5
Nexans ref. 25002BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 5
- Conductor cross-section: 1.5 mm²
- Approximate weight: 250 kg/km
- Nominal outer diameter: 13.0 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Permissible current rating in open air: 23 A
- Permissible current rating when buried: 21 A
- Voltage drop, 3 conductors: 22.8 V/A.km
5x10
Nexans ref. 25010BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 5
- Conductor cross-section: 10 mm²
- Approximate weight: 760 kg/km
- Nominal outer diameter: 20.0 mm
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Permissible current rating in open air: 75 A
- Permissible current rating when buried: 65 A
- Voltage drop, 3 conductors: 3.5 V/A.km
5x16
Nexans ref. 25016BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 5
- Conductor cross-section: 16 mm²
- Approximate weight: 1090 kg/km
- Nominal outer diameter: 22.0 mm
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Permissible current rating in open air: 100 A
- Permissible current rating when buried: 84 A
- Voltage drop, 3 conductors: 2.2 V/A.km
5x2.5
Nexans ref. 25003BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 5
- Conductor cross-section: 2.5 mm²
- Approximate weight: 310 kg/km
- Nominal outer diameter: 15.0 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 32 A
- Permissible current rating when buried: 30 A
- Voltage drop, 3 conductors: 14.0 V/A.km
5x25
Nexans ref. 25025BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 5
- Conductor cross-section: 25 mm²
- Approximate weight: 1630 kg/km
- Nominal outer diameter: 27.0 mm
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Permissible current rating in open air: 127 A
- Permissible current rating when buried: 107 A
- Voltage drop, 3 conductors: 1.5 V/A.km
5x35
Nexans ref. 25035BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 5
- Conductor cross-section: 35 mm²
- Approximate weight: 2610 kg/km
- Nominal outer diameter: 30.0 mm
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Permissible current rating in open air: 158 A
- Permissible current rating when buried: 129 A
- Voltage drop, 3 conductors: 1.1 V/A.km
5x4
Nexans ref. 25004BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 5
- Conductor cross-section: 4 mm²
- Approximate weight: 410 kg/km
- Nominal outer diameter: 16.0 mm
- Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
- Permissible current rating in open air: 42 A
- Permissible current rating when buried: 39 A
- Voltage drop, 3 conductors: 8.7 V/A.km
5x50
Nexans ref. 25050BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 5
- Conductor cross-section: 50 mm²
- Approximate weight: 2480 kg/km
- Nominal outer diameter: 33.0 mm
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Permissible current rating in open air: 192 A
- Permissible current rating when buried: 153 A
- Voltage drop, 3 conductors: 0.81 V/A.km
5x6
Nexans ref. 25006BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 5
- Conductor cross-section: 6 mm²
- Approximate weight: 530 kg/km
- Nominal outer diameter: 17.0 mm
- Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
- Permissible current rating in open air: 54 A
- Permissible current rating when buried: 49 A
- Voltage drop, 3 conductors: 5.9 V/A.km
5x70
Nexans ref. 25070BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 5
- Conductor cross-section: 70 mm²
- Approximate weight: 3480 kg/km
- Nominal outer diameter: 39.0 mm
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Permissible current rating in open air: 246 A
- Permissible current rating when buried: 188 A
- Voltage drop, 3 conductors: 0.58 V/A.km
7x1.5
Nexans ref. 2C002BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 7
- Conductor cross-section: 1.5 mm²
- Approximate weight: 340 kg/km
- Nominal outer diameter: 15.0 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Permissible current rating in open air: 23 A
- Permissible current rating when buried: 21 A
- Voltage drop, 3 conductors: 22.8 V/A.km
7x2.5
Nexans ref. 2C003BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 7
- Conductor cross-section: 2.5 mm²
- Approximate weight: 450 kg/km
- Nominal outer diameter: 17.0 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 32 A
- Permissible current rating when buried: 30 A
- Voltage drop, 3 conductors: 14.0 V/A.km
9x1.5
Nexans ref. 2K002BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 9
- Conductor cross-section: 1.5 mm²
- Approximate weight: 410 kg/km
- Nominal outer diameter: 16.0 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Permissible current rating in open air: 23 A
- Permissible current rating when buried: 21 A
- Voltage drop, 3 conductors: 22.8 V/A.km
9x2.5
Nexans ref. 2K003BXZOUB09BD0
- Packaging: Drum (m)
- Number of cores: 9
- Conductor cross-section: 2.5 mm²
- Approximate weight: 545 kg/km
- Nominal outer diameter: 18.0 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 32 A
- Permissible current rating when buried: 30 A
- Voltage drop, 3 conductors: 14.0 V/A.km
Description
Description
Standards
-
InternationalIEC 60332-1; IEC 60502-1
-
NationalMEW - LV Kuwait; SEC,11-SMDS-01,Rev.02
Application
These power cables are used for electricity supply in low voltage installation systems.
The cables are fully complyin to IEC and SEC, 1-SDMS-01, Rev.02 from KSA.
They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant…)
Design
- Conductor
Stranded bare copper class 2 acc. to IEC 60228
- Insulation
Cross Linked Polyethylene "XLPE"
- Outer Sheath
Polyvinyl Chloride "PVC"
Options:
- Flame retardant, Option "CAT A, CAT B, CAT C" to IEC60332 or equivalent.
- Ozone resistant.
- Oil resistant.
- Anti termite
Installation Conditions:
- Air Temperature : 30 Deg.
- Ground Temperature: 20 Deg.
- Soil Thermal Resistivity : 2.5 k.m/w
- Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %
Marking
no. of cores x conductor sizes mm2 Cu / XLPE / PVC 600/1000 V IEC 60502-1 MADE IN QATAR QICC-Nexans Year Meters
Custom marking available
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania