ALSECURE PLUS® NX300 BS LV, Mica, XLPE Insulation, HFFR 0.6/1 kV
ALSECURE PLUS® NX300 BS LV, Mica, XLPE Insulation, HFFR 0.6/1 kV
Unarmoured LV cable, HFFR sheathed for fixed installations. Rated voltage 0.6/1 KV
Read more2x1.5
Nexans ref. 22002FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 1.5 mm²
- Approximate weight: 265 kg/km
- Nominal outer diameter: 10.0 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Permissible current rating in open air: 23 A
- Permissible current rating when buried: 21 A
- Voltage drop, single phase: 22.8 V/A.km
3x 1.5
Nexans ref. 23002FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 3
- Conductor cross-section: 1.5 mm²
- Approximate weight: 160 kg/km
- Nominal outer diameter: 11.0 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Permissible current rating in open air: 23 A
- Permissible current rating when buried: 21 A
- Voltage drop, single phase: 22.8 V/A.km
4x 1.5
Nexans ref. 24002FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 4
- Conductor cross-section: 1.5 mm²
- Approximate weight: 190 kg/km
- Nominal outer diameter: 12.0 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Permissible current rating in open air: 23 A
- Permissible current rating when buried: 21 A
- Voltage drop, single phase: 22.8 V/A.km
5x 1.5
Nexans ref. 25002FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 5
- Conductor cross-section: 1.5 mm²
- Approximate weight: 220 kg/km
- Nominal outer diameter: 13.0 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Permissible current rating in open air: 23 A
- Permissible current rating when buried: 21 A
- Voltage drop, single phase: 22.8 V/A.km
2x 2.5
Nexans ref. 22003FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 2.5 mm²
- Approximate weight: 215 kg/km
- Nominal outer diameter: 11.0 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 32 A
- Permissible current rating when buried: 30 A
- Voltage drop, single phase: 14.0 V/A.km
3x 2.5
Nexans ref. 23003FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 3
- Conductor cross-section: 2.5 mm²
- Approximate weight: 200 kg/km
- Nominal outer diameter: 12.0 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 32 A
- Permissible current rating when buried: 30 A
- Voltage drop, single phase: 14.0 V/A.km
4x 2.5
Nexans ref. 24003FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 4
- Conductor cross-section: 2.5 mm²
- Approximate weight: 230 kg/km
- Nominal outer diameter: 13.0 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 32 A
- Permissible current rating when buried: 30 A
- Voltage drop, single phase: 14.0 V/A.km
5x 2.5
Nexans ref. 25003FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 5
- Conductor cross-section: 2.5 mm²
- Approximate weight: 270 kg/km
- Nominal outer diameter: 14.0 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 32 A
- Permissible current rating when buried: 30 A
- Voltage drop, single phase: 14.0 V/A.km
2x 4
Nexans ref. 22004FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 4 mm²
- Approximate weight: 170 kg/km
- Nominal outer diameter: 12.0 mm
- Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
- Permissible current rating in open air: 42 A
- Permissible current rating when buried: 39 A
- Voltage drop, single phase: 8.7 V/A.km
3x 4
Nexans ref. 23004FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 3
- Conductor cross-section: 4 mm²
- Approximate weight: 250 kg/km
- Nominal outer diameter: 13.0 mm
- Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
- Permissible current rating in open air: 42 A
- Permissible current rating when buried: 39 A
- Voltage drop, single phase: 8.7 V/A.km
4x 4
Nexans ref. 24004FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 4
- Conductor cross-section: 4 mm²
- Approximate weight: 300 kg/km
- Nominal outer diameter: 14.0 mm
- Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
- Permissible current rating in open air: 42 A
- Permissible current rating when buried: 39 A
- Voltage drop, single phase: 8.7 V/A.km
5x 4
Nexans ref. 25004FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 5
- Conductor cross-section: 4 mm²
- Approximate weight: 350 kg/km
- Nominal outer diameter: 15.0 mm
- Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
- Permissible current rating in open air: 42 A
- Permissible current rating when buried: 39 A
- Voltage drop, single phase: 8.7 V/A.km
2x 6
Nexans ref. 22006FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 6 mm²
- Approximate weight: 140 kg/km
- Nominal outer diameter: 13.0 mm
- Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
- Permissible current rating in open air: 54 A
- Permissible current rating when buried: 49 A
- Voltage drop, single phase: 5.9 V/A.km
3x 6
Nexans ref. 23006FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 3
- Conductor cross-section: 6 mm²
- Approximate weight: 320 kg/km
- Nominal outer diameter: 14.0 mm
- Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
- Permissible current rating in open air: 54 A
- Permissible current rating when buried: 49 A
- Voltage drop, single phase: 5.9 V/A.km
4x 6
Nexans ref. 24006FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 4
- Conductor cross-section: 6 mm²
- Approximate weight: 390 kg/km
- Nominal outer diameter: 15.0 mm
- Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
- Permissible current rating in open air: 54 A
- Permissible current rating when buried: 49 A
- Voltage drop, single phase: 5.9 V/A.km
5x 6
Nexans ref. 25006FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 5
- Conductor cross-section: 6 mm²
- Approximate weight: 465 kg/km
- Nominal outer diameter: 16.0 mm
- Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
- Permissible current rating in open air: 54 A
- Permissible current rating when buried: 49 A
- Voltage drop, single phase: 5.9 V/A.km
2x10
Nexans ref. 22010FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 10 mm²
- Approximate weight: 380 kg/km
- Nominal outer diameter: 15.0 mm
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Permissible current rating in open air: 75 A
- Permissible current rating when buried: 65 A
- Voltage drop, single phase: 3.5 V/A.km
3x10
Nexans ref. 23010FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 3
- Conductor cross-section: 10 mm²
- Approximate weight: 450 kg/km
- Nominal outer diameter: 16.0 mm
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Permissible current rating in open air: 75 A
- Permissible current rating when buried: 65 A
- Voltage drop, single phase: 3.5 V/A.km
4x10
Nexans ref. 24010FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 4
- Conductor cross-section: 10 mm²
- Approximate weight: 550 kg/km
- Nominal outer diameter: 17.0 mm
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Permissible current rating in open air: 75 A
- Permissible current rating when buried: 65 A
- Voltage drop, single phase: 3.5 V/A.km
5x10
Nexans ref. 25010FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 5
- Conductor cross-section: 10 mm²
- Approximate weight: 670 kg/km
- Nominal outer diameter: 19.0 mm
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Permissible current rating in open air: 75 A
- Permissible current rating when buried: 65 A
- Voltage drop, single phase: 3.5 V/A.km
2x16
Nexans ref. 22016FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 16 mm²
- Approximate weight: 500 kg/km
- Nominal outer diameter: 17.0 mm
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Permissible current rating in open air: 100 A
- Permissible current rating when buried: 84 A
- Voltage drop, single phase: 2.2 V/A.km
3x16
Nexans ref. 23016FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 3
- Conductor cross-section: 16 mm²
- Approximate weight: 635 kg/km
- Nominal outer diameter: 18.0 mm
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Permissible current rating in open air: 100 A
- Permissible current rating when buried: 84 A
- Voltage drop, single phase: 2.2 V/A.km
4x16
Nexans ref. 24016FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 4
- Conductor cross-section: 16 mm²
- Approximate weight: 780 kg/km
- Nominal outer diameter: 19.0 mm
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Permissible current rating in open air: 100 A
- Permissible current rating when buried: 84 A
- Voltage drop, single phase: 2.2 V/A.km
5x16
Nexans ref. 25016FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 5
- Conductor cross-section: 16 mm²
- Approximate weight: 955 kg/km
- Nominal outer diameter: 21.0 mm
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Permissible current rating in open air: 100 A
- Permissible current rating when buried: 84 A
- Voltage drop, single phase: 2.2 V/A.km
2x25
Nexans ref. 22025FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 25 mm²
- Approximate weight: 730 kg/km
- Nominal outer diameter: 20.0 mm
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Permissible current rating in open air: 127 A
- Permissible current rating when buried: 107 A
- Voltage drop, single phase: 1.5 V/A.km
3x25
Nexans ref. 23025FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 3
- Conductor cross-section: 25 mm²
- Approximate weight: 930 kg/km
- Nominal outer diameter: 21.0 mm
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Permissible current rating in open air: 127 A
- Permissible current rating when buried: 107 A
- Voltage drop, single phase: 1.5 V/A.km
4x25
Nexans ref. 24025FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 4
- Conductor cross-section: 25 mm²
- Approximate weight: 1160 kg/km
- Nominal outer diameter: 23.0 mm
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Permissible current rating in open air: 127 A
- Permissible current rating when buried: 107 A
- Voltage drop, single phase: 1.5 V/A.km
5x25
Nexans ref. 25025FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 5
- Conductor cross-section: 25 mm²
- Approximate weight: 1425 kg/km
- Nominal outer diameter: 25.0 mm
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Permissible current rating in open air: 127 A
- Permissible current rating when buried: 107 A
- Voltage drop, single phase: 1.5 V/A.km
2x35
Nexans ref. 22035FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 35 mm²
- Approximate weight: 940 kg/km
- Nominal outer diameter: 22.0 mm
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Permissible current rating in open air: 158 A
- Permissible current rating when buried: 129 A
- Voltage drop, single phase: 1.1 V/A.km
3x35
Nexans ref. 23035FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 3
- Conductor cross-section: 35 mm²
- Approximate weight: 1200 kg/km
- Nominal outer diameter: 23.0 mm
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Permissible current rating in open air: 158 A
- Permissible current rating when buried: 129 A
- Voltage drop, single phase: 1.1 V/A.km
4x35
Nexans ref. 24035FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 4
- Conductor cross-section: 35 mm²
- Approximate weight: 1515 kg/km
- Nominal outer diameter: 25.0 mm
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Permissible current rating in open air: 158 A
- Permissible current rating when buried: 129 A
- Voltage drop, single phase: 1.1 V/A.km
5x35
Nexans ref. 25035FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 5
- Conductor cross-section: 35 mm²
- Approximate weight: 2280 kg/km
- Nominal outer diameter: 28.0 mm
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Permissible current rating in open air: 158 A
- Permissible current rating when buried: 129 A
- Voltage drop, single phase: 1.1 V/A.km
1x50
Nexans ref. 21050RXZOUH34BD0
- Conductor shape: Circular
- Number of cores: 1
- Conductor cross-section: 50 mm²
- Approximate weight: 700 kg/km
- Nominal outer diameter: 14.0 mm
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Permissible current rating in open air: 216 A
- Permissible current rating when buried: 153 A
- Voltage drop, single phase: 0.84 V/A.km
2x50
Nexans ref. 22050FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 50 mm²
- Approximate weight: 1220 kg/km
- Nominal outer diameter: 24.0 mm
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Permissible current rating in open air: 192 A
- Permissible current rating when buried: 153 A
- Voltage drop, single phase: 0.81 V/A.km
3x50
Nexans ref. 23050FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 3
- Conductor cross-section: 50 mm²
- Approximate weight: 1250 kg/km
- Nominal outer diameter: 22.0 mm
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Permissible current rating in open air: 192 A
- Permissible current rating when buried: 153 A
- Voltage drop, single phase: 0.81 V/A.km
4x50
Nexans ref. 24050FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 4
- Conductor cross-section: 50 mm²
- Approximate weight: 1620 kg/km
- Nominal outer diameter: 24.0 mm
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Permissible current rating in open air: 192 A
- Permissible current rating when buried: 153 A
- Voltage drop, single phase: 0.81 V/A.km
5x50
Nexans ref. 25050FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 5
- Conductor cross-section: 50 mm²
- Approximate weight: 2170 kg/km
- Nominal outer diameter: 32.0 mm
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Permissible current rating in open air: 192 A
- Permissible current rating when buried: 153 A
- Voltage drop, single phase: 0.81 V/A.km
1x70
Nexans ref. 21070RXZOUH34BD0
- Conductor shape: Circular
- Number of cores: 1
- Conductor cross-section: 70 mm²
- Approximate weight: 900 kg/km
- Nominal outer diameter: 16.0 mm
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Permissible current rating in open air: 278 A
- Permissible current rating when buried: 188 A
- Voltage drop, single phase: 0.61 V/A.km
2x70
Nexans ref. 22070FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 70 mm²
- Approximate weight: 1700 kg/km
- Nominal outer diameter: 28.0 mm
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Permissible current rating in open air: 246 A
- Permissible current rating when buried: 188 A
- Voltage drop, single phase: 0.58 V/A.km
3x70
Nexans ref. 23070FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 3
- Conductor cross-section: 70 mm²
- Approximate weight: 1770 kg/km
- Nominal outer diameter: 25.0 mm
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Permissible current rating in open air: 246 A
- Permissible current rating when buried: 188 A
- Voltage drop, single phase: 0.58 V/A.km
4x70
Nexans ref. 24070FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 4
- Conductor cross-section: 70 mm²
- Approximate weight: 2300 kg/km
- Nominal outer diameter: 28.0 mm
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Permissible current rating in open air: 246 A
- Permissible current rating when buried: 188 A
- Voltage drop, single phase: 0.58 V/A.km
5x70
Nexans ref. 25070FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 5
- Conductor cross-section: 70 mm²
- Approximate weight: 3050 kg/km
- Nominal outer diameter: 37.0 mm
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Permissible current rating in open air: 246 A
- Permissible current rating when buried: 188 A
- Voltage drop, single phase: 0.58 V/A.km
1x95
Nexans ref. 21095RXZOUH34BD0
- Conductor shape: Circular
- Number of cores: 1
- Conductor cross-section: 95 mm²
- Approximate weight: 1160 kg/km
- Nominal outer diameter: 18.0 mm
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Permissible current rating in open air: 342 A
- Permissible current rating when buried: 226 A
- Voltage drop, single phase: 0.47 V/A.km
2x95
Nexans ref. 22095FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 95 mm²
- Approximate weight: 2280 kg/km
- Nominal outer diameter: 32.0 mm
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Permissible current rating in open air: 298 A
- Permissible current rating when buried: 226 A
- Voltage drop, single phase: 0.44 V/A.km
3x95
Nexans ref. 23095FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 3
- Conductor cross-section: 95 mm²
- Approximate weight: 2390 kg/km
- Nominal outer diameter: 29.0 mm
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Permissible current rating in open air: 298 A
- Permissible current rating when buried: 226 A
- Voltage drop, single phase: 0.44 V/A.km
4x95
Nexans ref. 24095FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 4
- Conductor cross-section: 95 mm²
- Approximate weight: 2280 kg/km
- Nominal outer diameter: 31.0 mm
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Permissible current rating in open air: 298 A
- Permissible current rating when buried: 226 A
- Voltage drop, single phase: 0.44 V/A.km
1x120
Nexans ref. 21120RXZOUH34BD0
- Conductor shape: Circular
- Number of cores: 1
- Conductor cross-section: 120 mm²
- Approximate weight: 1400 kg/km
- Nominal outer diameter: 20.0 mm
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Permissible current rating in open air: 400 A
- Permissible current rating when buried: 257 A
- Voltage drop, single phase: 0.39 V/A.km
2x120
Nexans ref. 22120FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 120 mm²
- Approximate weight: 2830 kg/km
- Nominal outer diameter: 35.0 mm
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Permissible current rating in open air: 346 A
- Permissible current rating when buried: 257 A
- Voltage drop, single phase: 0.37 V/A.km
3x120
Nexans ref. 23120FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 3
- Conductor cross-section: 120 mm²
- Approximate weight: 3000 kg/km
- Nominal outer diameter: 32.0 mm
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Permissible current rating in open air: 346 A
- Permissible current rating when buried: 257 A
- Voltage drop, single phase: 0.37 V/A.km
4x120
Nexans ref. 24120FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 4
- Conductor cross-section: 120 mm²
- Approximate weight: 3910 kg/km
- Nominal outer diameter: 35.0 mm
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Permissible current rating in open air: 346 A
- Permissible current rating when buried: 257 A
- Voltage drop, single phase: 0.37 V/A.km
1x150
Nexans ref. 21150RXZOUH34BD0
- Conductor shape: Circular
- Number of cores: 1
- Conductor cross-section: 150 mm²
- Approximate weight: 1700 kg/km
- Nominal outer diameter: 21.0 mm
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Permissible current rating in open air: 464 A
- Permissible current rating when buried: 287 A
- Voltage drop, single phase: 0.34 V/A.km
2x150
Nexans ref. 22150FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 150 mm²
- Approximate weight: 3465 kg/km
- Nominal outer diameter: 39.0 mm
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Permissible current rating in open air: 399 A
- Permissible current rating when buried: 287 A
- Voltage drop, single phase: 0.31 V/A.km
3x150
Nexans ref. 23150FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 3
- Conductor cross-section: 150 mm²
- Approximate weight: 3700 kg/km
- Nominal outer diameter: 35.0 mm
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Permissible current rating in open air: 399 A
- Permissible current rating when buried: 287 A
- Voltage drop, single phase: 0.31 V/A.km
4x150
Nexans ref. 24150FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 4
- Conductor cross-section: 150 mm²
- Approximate weight: 4830 kg/km
- Nominal outer diameter: 39.0 mm
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Permissible current rating in open air: 399 A
- Permissible current rating when buried: 287 A
- Voltage drop, single phase: 0.31 V/A.km
1x185
Nexans ref. 21185RXZOUH34BD0
- Conductor shape: Circular
- Number of cores: 1
- Conductor cross-section: 185 mm²
- Approximate weight: 2050 kg/km
- Nominal outer diameter: 23.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Permissible current rating in open air: 533 A
- Permissible current rating when buried: 324 A
- Voltage drop, single phase: 0.29 V/A.km
2x185
Nexans ref. 22185FXZOUB09BD0
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 185 mm²
- Approximate weight: 4350 kg/km
- Nominal outer diameter: 44.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Permissible current rating in open air: 456 A
- Permissible current rating when buried: 324 A
- Voltage drop, single phase: 0.27 V/A.km
3x185
Nexans ref. 23185FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 3
- Conductor cross-section: 185 mm²
- Approximate weight: 4590 kg/km
- Nominal outer diameter: 39.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Permissible current rating in open air: 456 A
- Permissible current rating when buried: 324 A
- Voltage drop, single phase: 0.27 V/A.km
4x185
Nexans ref. 24185FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 4
- Conductor cross-section: 185 mm²
- Approximate weight: 6030 kg/km
- Nominal outer diameter: 43.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
- Permissible current rating in open air: 456 A
- Permissible current rating when buried: 324 A
- Voltage drop, single phase: 0.27 V/A.km
1x240
Nexans ref. 21240RXZOUH34BD0
- Conductor shape: Circular
- Number of cores: 1
- Conductor cross-section: 240 mm²
- Approximate weight: 2550 kg/km
- Nominal outer diameter: 26.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- Permissible current rating in open air: 634 A
- Permissible current rating when buried: 375 A
- Voltage drop, single phase: 0.25 V/A.km
3x240
Nexans ref. 23240FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 3
- Conductor cross-section: 240 mm²
- Approximate weight: 5880 kg/km
- Nominal outer diameter: 43.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- Permissible current rating in open air: 538 A
- Permissible current rating when buried: 375 A
- Voltage drop, single phase: 0.23 V/A.km
4x240
Nexans ref. 24240FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 4
- Conductor cross-section: 240 mm²
- Approximate weight: 7850 kg/km
- Nominal outer diameter: 49.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
- Permissible current rating in open air: 538 A
- Permissible current rating when buried: 375 A
- Voltage drop, single phase: 0.23 V/A.km
1x300
Nexans ref. 21340RXZOUH34BD0
- Conductor shape: Circular
- Number of cores: 1
- Conductor cross-section: 300 mm²
- Approximate weight: 3100 kg/km
- Nominal outer diameter: 28.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
- Permissible current rating in open air: 736 A
- Permissible current rating when buried: 419 A
- Voltage drop, single phase: 0.22 V/A.km
3x300
Nexans ref. 23300FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 3
- Conductor cross-section: 300 mm²
- Approximate weight: 7380 kg/km
- Nominal outer diameter: 48.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
- Permissible current rating in open air: 621 A
- Permissible current rating when buried: 419 A
- Voltage drop, single phase: 0.2 V/A.km
4x300
Nexans ref. 24300FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 4
- Conductor cross-section: 300 mm²
- Approximate weight: 9850 kg/km
- Nominal outer diameter: 55.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
- Permissible current rating in open air: 621 A
- Permissible current rating when buried: 419 A
- Voltage drop, single phase: 0.2 V/A.km
1x400
Nexans ref. 21400RXZOUH34BD0
- Conductor shape: Circular
- Number of cores: 1
- Conductor cross-section: 400 mm²
- Approximate weight: 4000 kg/km
- Nominal outer diameter: 32.0 mm
- Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
- Permissible current rating in open air: 868 A
- Permissible current rating when buried: 717 A
- Voltage drop, single phase: 0.19 V/A.km
3x400
Nexans ref. 23400FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 3
- Conductor cross-section: 400 mm²
- Approximate weight: 9440 kg/km
- Nominal outer diameter: 55.0 mm
- Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
- Permissible current rating in open air: 765 A
- Permissible current rating when buried: 468 A
- Voltage drop, single phase: 0.18 V/A.km
4x400
Nexans ref. 24400FXZOUB09BD0
- Conductor shape: Sector-shaped
- Number of cores: 4
- Conductor cross-section: 400 mm²
- Approximate weight: 12555 kg/km
- Nominal outer diameter: 61.0 mm
- Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
- Permissible current rating in open air: 765 A
- Permissible current rating when buried: 468 A
- Voltage drop, single phase: 0.18 V/A.km
1x500
Nexans ref. 21500RXZOUH34BD0
- Conductor shape: Circular
- Number of cores: 1
- Conductor cross-section: 500 mm²
- Approximate weight: 5020 kg/km
- Nominal outer diameter: 24.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0366 Ohm/km
- Permissible current rating in open air: 998 A
- Permissible current rating when buried: 791 A
- Voltage drop, single phase: 0.17 V/A.km
1x630
Nexans ref. 21634RXZOUH34BD0
- Conductor shape: Circular
- Number of cores: 1
- Conductor cross-section: 630 mm²
- Approximate weight: 6200 kg/km
- Nominal outer diameter: 41.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0283 Ohm/km
- Permissible current rating in open air: 1151 A
- Permissible current rating when buried: 861 A
- Voltage drop, single phase: 0.16 V/A.km
1x800
Nexans ref. 21800RXZOUH34BD0
- Conductor shape: Circular
- Number of cores: 1
- Conductor cross-section: 800 mm²
- Approximate weight: 8000 kg/km
- Nominal outer diameter: 45.0 mm
- Max. DC resistance of the conductor at 20°C: 0.0221 Ohm/km
- Permissible current rating in open air: 1246 A
- Permissible current rating when buried: 904 A
- Voltage drop, single phase: 0.15 V/A.km
Description
Description
Standards
-
ProductBS 6724
-
TestIEC 60332-1
Application
These power cables are used for electricity supply in low voltage installation systems.
They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant…)
Design
- Conductor
Stranded bare copper class 2 acc. to IEC 60228
- Fire Barrier
Mica Glass tape
- Insulation
Cross Linked Polyethylene "XLPE"
- Outer Sheath
Halogen Free Flame retardant "HFFR".
Options :
- Flame retardant : "CAT A, CAT B, CAT C" to BS 4066 or equivalent.
- Ozone resistant.
- Oil resistant.
- Anti termite.
Fire test :
As per BS 6387 :
C-Resistance to fire at 950 Deg for 180 mins.
W-Resistanace to fire and water at 650 Deg for 30 mins.
Z-Resistance to fire and mechanical shock at 950 Deg for 15 mins.
Installation Conditions:
- Air Temperature : 30 Deg.
- Ground Temperature: 20 Deg.
- Soil Thermal Resistivity : 2.5 k.m/w
- Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Selling & delivery Information
Marking
no. of cores x conductor sizes mm2 Cu / Mica / XLPE / HFFR 600/1000 V BS 6724 MADE IN QATAR QICC-Nexans Year Meters
Custom marking available
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania