ALSECURE PLUS® NX100 BS, Cu/Mica/XL-HFFR
ALSECURE PLUS® NX100 BS, Cu/Mica/XL-HFFR
600/1000V Fire resistant, halogen free, flame retardant earthing wires
Read more1x2.5
Nexans ref. 21003PHZOU000BD0
- Conductor cross-section: 2.5 mm²
- Nominal outer diameter: 3.7 mm
- Approximate weight: 30 kg/km
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 43 A
- Voltage Drop: 13.8 V/A.km
1x4
Nexans ref. 21004PHZOU000BD0
- Conductor cross-section: 4 mm²
- Nominal outer diameter: 4.2 mm
- Approximate weight: 40 kg/km
- Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
- Permissible current rating in open air: 56 A
- Voltage Drop: 8.6 V/A.km
1x6
Nexans ref. 21006PHZOU000BD0
- Conductor cross-section: 6 mm²
- Nominal outer diameter: 4.8 mm
- Approximate weight: 60 kg/km
- Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
- Permissible current rating in open air: 71 A
- Voltage Drop: 5.8 V/A.km
1x10
Nexans ref. 21010PHZOU000BD0
- Conductor cross-section: 10 mm²
- Nominal outer diameter: 6.0 mm
- Approximate weight: 110 kg/km
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Permissible current rating in open air: 97 A
- Voltage Drop: 3.5 V/A.km
1x16
Nexans ref. 21016PHZOU000BD0
- Conductor cross-section: 16 mm²
- Nominal outer diameter: 6.5 mm
- Approximate weight: 170 kg/km
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Permissible current rating in open air: 130 A
- Voltage Drop: 2.2 V/A.km
1x25
Nexans ref. 21025PHZOU000BD0
- Conductor cross-section: 25 mm²
- Nominal outer diameter: 8.5 mm
- Approximate weight: 260 kg/km
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Permissible current rating in open air: 171 A
- Voltage Drop: 1.4 V/A.km
1x35
Nexans ref. 21035PHZOU000BD0
- Conductor cross-section: 35 mm²
- Nominal outer diameter: 9.5 mm
- Approximate weight: 360 kg/km
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Permissible current rating in open air: 210 A
- Voltage Drop: 1.1 V/A.km
1x50
Nexans ref. 21050PHZOU000BD0
- Conductor cross-section: 50 mm²
- Nominal outer diameter: 11.0 mm
- Approximate weight: 480 kg/km
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Permissible current rating in open air: 262 A
- Voltage Drop: 0.8 V/A.km
1x70
Nexans ref. 21070PHZOU000BD0
- Conductor cross-section: 70 mm²
- Nominal outer diameter: 13.0 mm
- Approximate weight: 650 kg/km
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Permissible current rating in open air: 325 A
- Voltage Drop: 0.58 V/A.km
1x95
Nexans ref. 21095PHZOU000BD0
- Conductor cross-section: 95 mm²
- Nominal outer diameter: 15.0 mm
- Approximate weight: 950 kg/km
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Permissible current rating in open air: 387 A
- Voltage Drop: 0.44 V/A.km
1x120
Nexans ref. 21120PHZOU000BD0
- Conductor cross-section: 120 mm²
- Nominal outer diameter: 16.0 mm
- Approximate weight: 1200 kg/km
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Permissible current rating in open air: 456 A
- Voltage Drop: 0.37 V/A.km
1x150
Nexans ref. 21150PHZOU000BD0
- Conductor cross-section: 150 mm²
- Nominal outer diameter: 18.0 mm
- Approximate weight: 1400 kg/km
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Permissible current rating in open air: 518 A
- Voltage Drop: 0.32 V/A.km
1x185
Nexans ref. 21185PHZOU000BD0
- Conductor cross-section: 185 mm²
- Nominal outer diameter: 20.0 mm
- Approximate weight: 1800 kg/km
- Max. DC resistance of the conductor at 20°C: 0.099 Ohm/km
- Permissible current rating in open air: 593 A
- Voltage Drop: 0.27 V/A.km
1x240
Nexans ref. 21240PHZOU000BD0
- Conductor cross-section: 240 mm²
- Nominal outer diameter: 23.0 mm
- Approximate weight: 2970 kg/km
- Max. DC resistance of the conductor at 20°C: 0.075 Ohm/km
- Permissible current rating in open air: 700 A
- Voltage Drop: 0.23 V/A.km
1x300
Nexans ref. 21300PHZOU000BD0
- Conductor cross-section: 300 mm²
- Nominal outer diameter: 26.0 mm
- Approximate weight: 3600 kg/km
- Max. DC resistance of the conductor at 20°C: 0.06 Ohm/km
- Permissible current rating in open air: 806 A
- Voltage Drop: 0.2 V/A.km
1x400
Nexans ref. 21400PHZOU000BD0
- Conductor cross-section: 400 mm²
- Nominal outer diameter: 29.0 mm
- Approximate weight: 4600 kg/km
- Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
- Permissible current rating in open air: 962 A
- Voltage Drop: 0.18 V/A.km
1x500
Nexans ref. 21500PHZOU000BD0
- Conductor cross-section: 500 mm²
- Nominal outer diameter: 33.0 mm
- Approximate weight: 5970 kg/km
- Max. DC resistance of the conductor at 20°C: 0.037 Ohm/km
- Permissible current rating in open air: 1100 A
- Voltage Drop: 0.15 V/A.km
1x630
Nexans ref. 21630PHZOU000BD0
- Conductor cross-section: 630 mm²
- Nominal outer diameter: 36.0 mm
- Approximate weight: 7350 kg/km
- Max. DC resistance of the conductor at 20°C: 0.028 Ohm/km
- Permissible current rating in open air: 1227 A
- Voltage Drop: 0.14 V/A.km
1x800
Nexans ref. 21800PHZOU000BD0
- Conductor cross-section: 800 mm²
- Nominal outer diameter: 39.0 mm
- Approximate weight: 7600 kg/km
- Max. DC resistance of the conductor at 20°C: 0.022 Ohm/km
- Permissible current rating in open air: 1290 A
- Voltage Drop: 0.13 V/A.km
Description
Description
Standards
-
ProductBS 7211; EN 50525-3-41
Application:
Used in energy networks in refineries,mines,hotels,schools,tunnels,high constructions,hospitals,power plants, data processing centers,business centers where there is a risk of fire.
- Conductor
Stranded bare copper class 2 to BS EN 60228
- Fire barrier
Mica Glass Tape
- Insulation
Cross Linked Halogen Free "XL-HFFR"
Installation
In conduit, insulated support, ducts...in coverd and dry place.
Packing
The packing will be in coils with 91.4 m.
Marking:
450/750 V Cu/Mica/XL-FFR no. of cores x cable size H07Z-R EN 50525-3.41 LPCB Made in Qatar
Permissible current and voltage drop are given
For conductor laid alone in insulating tube on a wall Temperature = 30°C.
Permanent operation If conditions are different, apply correction factors from IEC 60364-5-52 standard or other equivalent national standard Voltage drop Calculated with cosj = 0,8
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania