ALSECURE® BS LV, XLPE Insulation, SWA, HFFR 0.6/1 kV
ALSECURE® BS LV, XLPE Insulation, SWA, HFFR 0.6/1 kV
Galvanized steel wire armoured LV cable, HFFR sheathed for fixed installations. Rated voltage 0.6/1 KV
Read more2x1.5
Nexans ref. 22002SXZHSH30BD0
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 1.5 mm²
- Approximate weight: 240 kg/km
- Nominal outer diameter: 11.0 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Permissible current rating in open air: 25 A
- Permissible current rating when buried: 23 A
- Voltage drop, 3 conductors: 22.8 V/A.km
2x10
Nexans ref. 22010SXZHSH30BD0
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 10 mm²
- Approximate weight: 600 kg/km
- Nominal outer diameter: 16.0 mm
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Permissible current rating in open air: 78 A
- Permissible current rating when buried: 65 A
- Voltage drop, 3 conductors: 3.5 V/A.km
2x120
Nexans ref. 22120SXZHSH30BD0!
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 120 mm²
- Approximate weight: 3610 kg/km
- Nominal outer diameter: 37.0 mm
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Permissible current rating in open air: 353 A
- Permissible current rating when buried: 257 A
- Voltage drop, 3 conductors: 0.37 V/A.km
2x150
Nexans ref. 22150SXZHSH30BD0!
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 150 mm²
- Approximate weight: 4280 kg/km
- Nominal outer diameter: 40.0 mm
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Permissible current rating in open air: 406 A
- Permissible current rating when buried: 287 A
- Voltage drop, 3 conductors: 0.3 V/A.km
2x16
Nexans ref. 22016SXZHSH30BD0!
- Conductor shape: Circular
- Number of cores: 2
- Conductor cross-section: 16 mm²
- Approximate weight: 750 kg/km
- Nominal outer diameter: 18.0 mm
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Permissible current rating in open air: 99 A
- Permissible current rating when buried: 84 A
- Voltage drop, 3 conductors: 2.2 V/A.km
Description
Description
Standards
-
ProductBS 6724
-
TestIEC 60332-3 Cat.C
Application
These power cables are used for electricity supply in low voltage installation systems.
They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant…)
Design
- Conductor
Stranded bare copper class 2 acc. to IEC 60228
- Insulation
Cross Linked Polyethylene "XLPE"
- Inner Sheath or Bedding
Halogen Free Flame Retardant "HFFR"
- Armour
Galvanized Steel Wire Armour "SWA"
- Outer Sheath
Halogen Free Flame Retardant "HFFR", to BS 4066 or equivalent.
Installation Conditions:
- Air Temperature : 30 Deg.
- Ground Temperature: 20 Deg.
- Soil Thermal Resistivity : 2.5 k.m/w
- Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Selling & delivery Information
Marking
no. of cores x conductor sizes mm2 Cu / XLPE / SWA / HFFR 600/1000 V Standard MADE IN QATAR QICC-Nexans Year Meters
Custom marking available